Follow Us on Google+

Request A Price Quote:

NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
PAM333MG6-10-250VAC400 74193 H 3 9 E TX

CAGE Information

Code Company
74193 EATON CORP HEINEMANN PRODUCTS COMMER

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
AKPX POLE QUANTITY 3
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 130.0 ALL LOCATIONS
ADAT BODY WIDTH 2.240 INCHES MINIMUM AND 2.260 INCHES MAXIMUM
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.689 INCHES MINIMUM AND 2.813 INCHES MAXIMUM
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
THSD THREAD SERIES DESIGNATOR UNC
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
ADAQ BODY LENGTH 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
CPRW ACTUATOR FUNCTION TRIP-RESET
PKWT UNPACKAGED UNIT WEIGHT 9.500 OUNCES
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 THREADED STUD
AJEC BOSS HEIGHT 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 AC ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CMLP THREAD QUANTITY PER INCH 32
CQJX NOMINAL THREAD SIZE 0.138 INCHES

Similar Parts

PAM333MG6-10-250VAC400 , PAM333MG610250VAC400 , 5925-00-003-4722 , 5925000034722 , 000034722 , PAM333MG6-10-250VAC400 ,