Follow Us on Google+

Request A Price Quote:

NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
ETN275400S01 30086 A C 1 6 ZZ AC
ET86020 30086 A 3 2 A TX

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ADAT BODY WIDTH 4.500 INCHES NOMINAL
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 500.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
AKPX POLE QUANTITY 3
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.594 INCHES NOMINAL
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 120.0 ALL LOCATIONS
ADAU BODY HEIGHT 3.594 INCHES NOMINAL
CQJX NOMINAL THREAD SIZE 0.190 INCHES
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED MOISTURE RESISTANT AND FUNGUS RESISTANT AND SHOCKPROOF
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED STUD
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.500 INCHES NOMINAL
ADAQ BODY LENGTH 6.000 INCHES NOMINAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS
CPSF ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS +1200.0/+1400.0 AC ALL LOCATIONS AND +1200.0/+1400.0 DC ALL LOCATIONS
CBBL FEATURES PROVIDED ADJUSTABLE TRIP RELEASE
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
THSD THREAD SERIES DESIGNATOR UNF
AJEC BOSS HEIGHT 0.219 INCHES NOMINAL
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 100.0 AMPERES AC ALL LOCATIONS AND 100.0 AMPERES DC ALL LOCATIONS
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.500 INCHES NOMINAL
TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 5.125 INCHES NOMINAL
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CMLP THREAD QUANTITY PER INCH 32

Similar Parts

ET86020 , ET86020 , 5925-00-106-7185 , 5925001067185 , 001067185 , ETN275400S01 , ET86020 ,