NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
430055SUB7PT18 | 49671 | F | 5 | 9 | 5 | ZZ | ||
M430055-18 | 49671 | F | 5 | 9 | 5 | ZZ | ||
45533-2 | 96214 | A | 5 | 2 | 5 | TX | ||
7411422P2 | 03511 | A | 5 | 2 | 5 | TX | ||
PSM-3-N | 82647 | A | 3 | 2 | E | TX |
CAGE Information
Code | Company |
---|---|
03511 | GENERAL ELECTRIC CO SPECIALTY MOTOR |
49671 | LOCKHEED MARTIN CORP LOCKHEED MARTIN |
96214 | RAYTHEON COMPANY |
82647 | SENSATA TECHNOLOGIES INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 300.000 MINIMUM AT 125 PCT SINGLE LOCATION AND 30.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 300.000 MINIMUM AT 125 PCT SINGLE LOCATION AND 30.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.469 INCHES |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
AAQL | BODY STYLE | SINGLE POLE TYPE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 30.0 AC SINGLE LOCATION AND 30.0 DC SINGLE LOCATION |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
ABXD | BUSHING LENGTH | 0.312 INCHES NOMINAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
THSD | THREAD SERIES DESIGNATOR | UNS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 600.0 AC SINGLE LOCATION AND 600.0 DC SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | RESET |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.312 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
ADAQ | BODY LENGTH | 1.531 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES AC SINGLE LOCATION AND 3.0 AMPERES DC SINGLE LOCATION |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.407 INCHES NOMINAL |