NIIN Output Data
NIIN:
NSN:
Item Name:
CIRCUIT BREAKER
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number |
CAGE |
Status |
RNCC |
RNVC |
DAC |
RNAAC |
MSDS |
SADC |
999002 |
79500 |
A |
5 |
9 |
X |
AX |
|
|
776774371 |
24446 |
A |
3 |
2 |
X |
XX |
|
|
999002 |
90099 |
A |
3 |
2 |
6 |
AX |
|
|
CAGE Information
Code |
Company |
24446 |
GENERAL ELECTRIC CO |
79500 |
WESTINGHOUSE ELECTRIC CORP |
90099 |
NORTHROP GRUMMAN SYSTEMS CORPORATION |
Characteristics (Decoded)
MRC |
Requirements Statement |
Clear Text Reply |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SINGLE LOCATION |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SINGLE LOCATION |
TTQY |
TERMINAL TYPE AND QUANTITY |
1 SCREW |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
15.0 AMPERES AC SINGLE LOCATION AND 15.0 AMPERES DC SINGLE LOCATION |
ABKW |
OVERALL HEIGHT |
3.969 INCHES NOMINAL |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
125.0 AC SINGLE LOCATION AND 125.0 DC SINGLE LOCATION |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
ABMK |
OVERALL WIDTH |
1.375 INCHES NOMINAL |
AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.188 INCHES NOMINAL |
ADTV |
CASE MATERIAL |
PLASTIC |
AKPX |
POLE QUANTITY |
1 |
CPRQ |
RESET METHOD |
MANUAL |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
122.0 SINGLE LOCATION |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
5000.0 AC SINGLE LOCATION AND 5000.0 DC SINGLE LOCATION |
CPRJ |
TRIP RELEASE METHOD |
THERMAL SINGLE LOCATION |
APNQ |
ARC QUENCHING METHOD |
DEION |
CPRW |
ACTUATOR FUNCTION |
TRIP W/SEPARATE RESET |
FEAT |
SPECIAL FEATURES |
MTG HOLES DIAGONALLY SPACED ON 0.812 BY 4.844 IN. MTG CENTERS |
ABHP |
OVERALL LENGTH |
6.000 INCHES NOMINAL |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
7.000 MINIMUM AT 300 PCT SINGLE LOCATION AND 58.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 17.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 170.000 MINIMUM AT 125 PCT SINGLE LOCATION AND 3699.000 MAXIMUM AT 125 PCT SINGLE LOCATION AND 18.000 MAXIMUM AT 300 PCT SINGLE LOCATION |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY SINGLE LOCATION |
CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 UNTHREADED HOLE |
Similar Parts