Follow Us on Google+

Request A Price Quote:

NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
44A355500-001 30221 A 3 2 1 TX
AP3-279-1 81541 A 5 2 5 TX
44A355500P001 25583 A 3 2 5 9Z
44A355500-P1 89954 A 5 9 5 9Z
44A355500-P1 30221 A 5 9 5 9Z

CAGE Information

Code Company
25583 L-3 COMMUNICATIONS AVIONICS SYSTEMS
30221 GENERAL ELECTRIC CO ARMAMENT AND ELE
81541 SENSATA TECHNOLOGIES MARYLAND INC
89954 BAE SYSTEMS CONTROLS INC. DBA PLATFO

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.605 INCHES MAXIMUM
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.605 INCHES MAXIMUM
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 115.0 SINGLE LOCATION
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC SINGLE LOCATION AND 50.0 DC SINGLE LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 1 THREADED BUSHING
TTQY TERMINAL TYPE AND QUANTITY 2 TAB, SOLDER LUG
AAQL BODY STYLE SINGLE POLE TYPE
THSD THREAD SERIES DESIGNATOR UNEF
ABXD BUSHING LENGTH 0.380 INCHES NOMINAL
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CQJX NOMINAL THREAD SIZE 0.375 INCHES
CPRJ TRIP RELEASE METHOD MAGNETIC SINGLE LOCATION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.007 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.025 MAXIMUM AT 200 PCT SINGLE LOCATION
AKPX POLE QUANTITY 1
CPRQ RESET METHOD MANUAL
CPRW ACTUATOR FUNCTION RESET
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.875 INCHES NOMINAL
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED MOISTURE RESISTANT
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 20.0 AMPERES AC SINGLE LOCATION AND 20.0 AMPERES DC SINGLE LOCATION
ADAQ BODY LENGTH 1.500 INCHES MAXIMUM
ADTV CASE MATERIAL METAL
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CMLP THREAD QUANTITY PER INCH 32
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
ADAT BODY WIDTH 0.625 INCHES MAXIMUM
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 300.0 AC SINGLE LOCATION AND 500.0 DC SINGLE LOCATION

Similar Parts

44A355500P001 , 44A355500P001 , 5925-00-402-1158 , 5925004021158 , 004021158 , 44A355500-001 , AP3-279-1 , 44A355500P001 , 44A355500-P1 , 44A355500-P1 ,