NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
ET87229ET87230 | 30086 | A | 3 | 2 | 5 | HD | ||
0962-049-7010 | 80064 | A | 5 | 1 | E | TX |
CAGE Information
Code | Company |
---|---|
30086 | SPD ELECTRICAL SYSTEMS INC |
80064 | NAVAL SHIP SYSTEMS COMMAND |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 160.000 MINIMUM ALL LOCATIONS AND 2000.000 MAXIMUM ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AKPX | POLE QUANTITY | 3 |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 150.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 700.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 75000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.406 INCHES NOMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1600.0 AMPERES AC ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 PIN |