NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
ET4035 | 30086 | A | 3 | 2 | 5 | TX | ||
ET4035 | 60555 | H | 5 | 9 | 6 | TX | ||
PX1365 | 89564 | A | 5 | 9 | 5 | TX |
CAGE Information
Code | Company |
---|---|
30086 | SPD ELECTRICAL SYSTEMS INC |
60555 | SIEMENS-ALLIS INC |
89564 | VULCAN-HART CORP |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
AKPX | POLE QUANTITY | 3 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 75.000 NOMINAL AT 200 PCT ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 105.0 ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS AND 50.0 AMPERES DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |