NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
QC2015 | 97942 | A | 5 | 9 | 6 | TX | ||
QC2015/1265C83G02 | 89946 | A | 5 | 2 | E | ZZ | ||
HQCL2015 | 89946 | A | 5 | 9 | A | TX | ||
377D022G05 | 89946 | A | 5 | 9 | 3 | TX | ||
SM-C-623914 | 80063 | A | 3 | 2 | 5 | TX | ||
S656D022G05 | 89946 | A | 5 | 9 | 5 | TX | ||
183885 | 19139 | A | 5 | 2 | 5 | TX | ||
THQC2115/TQCFMP-2 | 60969 | A | 5 | 2 | E | ZZ | ||
QCL2015 | 89946 | A | 5 | 9 | 3 | TX | ||
QC2015 | 89946 | A | 5 | 9 | 6 | TX | ||
QCL2015 | 79500 | A | 5 | 9 | 3 | TX | ||
JR202 | 80531 | F | 5 | 9 | 5 | TX |
CAGE Information
Code | Company |
---|---|
19139 | EASTMAN KODAK COMPANY DBA KODAK |
97942 | NORTHROP GRUMMAN SYSTEMS CORPORATION |
89946 | EATON CORPORATION |
80063 | US ARMY COMMUNICATIONS & ELECTRONICS |
60969 | GENERAL ELECTRIC CO ELECTRICAL DISTR |
79500 | WESTINGHOUSE ELECTRIC CORP |
80531 | C AND D BATTERIES AN ALLIED CO PLANT |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
TTQY | TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |
AKPX | POLE QUANTITY | 2 |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CQJX | NOMINAL THREAD SIZE | 0.190 INCHES |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 35.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 450.000 MAXIMUM AT 150 PCT ALL LOCATIONS |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
ADAQ | BODY LENGTH | 3.750 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
THSD | THREAD SERIES DESIGNATOR | UNF |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
ADAT | BODY WIDTH | 2.000 INCHES NOMINAL |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAU | BODY HEIGHT | 2.500 INCHES NOMINAL |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CMLP | THREAD QUANTITY PER INCH | 32 |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |