Follow Us on Google+

Request A Price Quote:

NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
ETM1575 30086 A 5 9 6 TX
EE3M050 30086 A 3 2 E TX
EE3M050 60555 H 5 9 6 TX

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC
60555 SIEMENS-ALLIS INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 75.000 MINIMUM AT 125 PCT ALL LOCATIONS AND 240.000 MAXIMUM AT 200 PCT ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 4.594 INCHES NOMINAL
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ADAT BODY WIDTH 4.500 INCHES NOMINAL
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.594 INCHES NOMINAL
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.500 INCHES NOMINAL
ADAQ BODY LENGTH 6.000 INCHES NOMINAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
AJEC BOSS HEIGHT 0.219 INCHES NOMINAL
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.500 INCHES NOMINAL
ADAU BODY HEIGHT 3.219 INCHES NOMINAL
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.190 INCHES NOMINAL
TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 7500.0 AC ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED GENERAL PURPOSE
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 50.0 AMPERES AC ALL LOCATIONS

Similar Parts

EE3M050 , EE3M050 , 5925-00-783-6214 , 5925007836214 , 007836214 , ETM1575 , EE3M050 , EE3M050 ,