NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
711599-115 82577 A 3 2 5 TX
P3X1163SMG4-70-208VAC 74193 H 5 9 E TX

CAGE Information

Code Company
74193 EATON CORP HEINEMANN PRODUCTS COMMER
82577 RAYTHEON COMPANY DBA RAYTHEON

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.240 INCHES MINIMUM AND 1.260 INCHES MAXIMUM
AKPX POLE QUANTITY 3
AFJN FRAGILITY FACTOR MODERATELY RUGGED
ADAU BODY HEIGHT 2.678 INCHES MINIMUM AND 2.698 INCHES MAXIMUM
AJEC BOSS HEIGHT 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 208.0 AC ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.190 INCHES
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 130.0 ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
THSD THREAD SERIES DESIGNATOR UNF
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 3.052 INCHES MINIMUM AND 3.072 INCHES MAXIMUM
ADAQ BODY LENGTH 5.240 INCHES MINIMUM AND 5.260 INCHES MAXIMUM
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED HOLE AND 4 UNTHREADED HOLE
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.164 INCHES NOMINAL
ADAT BODY WIDTH 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM
CPRW ACTUATOR FUNCTION TRIP-RESET
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED SHOCKPROOF AND FUNGUS PROOF AND DUSTPROOF AND MOISTURE PROOF AND HUMIDITY PROOF AND VIBRATIONPROOF
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 THREADED STUD
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 70.0 AMPERES AC ALL LOCATIONS
PKWT UNPACKAGED UNIT WEIGHT 48.000 OUNCES
CMLP THREAD QUANTITY PER INCH 32

Similar Parts