NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
2263MG4-20-250VAC60C1 | 74193 | H | 5 | 9 | 6 | TX | ||
920555-1 | 06481 | A | 5 | 2 | 5 | TX | ||
2263MG4-20-250-60-1 | 74193 | H | 3 | 9 | E | TX |
CAGE Information
Code | Company |
---|---|
06481 | NORTHROP GRUMMAN GUIDANCE AND ELECTR |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
ADAT | BODY WIDTH | 1.990 INCHES MINIMUM AND 2.010 INCHES MAXIMUM |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
AJEC | BOSS HEIGHT | 0.208 INCHES MINIMUM AND 0.228 INCHES MAXIMUM |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
ADAU | BODY HEIGHT | 2.677 INCHES MINIMUM AND 2.697 INCHES MAXIMUM |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
AKPX | POLE QUANTITY | 2 |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.974 INCHES MINIMUM AND 0.994 INCHES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE AND 2 UNTHREADED HOLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 35.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 105.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 3.052 INCHES MINIMUM AND 3.072 INCHES MAXIMUM |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
THSD | THREAD SERIES DESIGNATOR | UNC |
ADAQ | BODY LENGTH | 5.240 INCHES MINIMUM AND 5.260 INCHES MAXIMUM |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CQJX | NOMINAL THREAD SIZE | 0.164 INCHES |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
CMLP | THREAD QUANTITY PER INCH | 32 |