Follow Us on Google+

Request A Price Quote:

NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
EH2070 89946 A 3 2 4 75
451D852G06 89946 A 5 2 4 75

CAGE Information

Code Company
89946 EATON CORPORATION

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CQQC TRIP RELEASE DUTY CYCLE CONTINUOUS ALL LOCATIONS
ABKW OVERALL HEIGHT 2.750 INCHES NOMINAL
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 70.0 AMPERES AC ALL LOCATIONS AND 70.0 AMPERES DC ALL LOCATIONS
AKPX POLE QUANTITY 2
THSD THREAD SERIES DESIGNATOR UN
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 4 SCREW
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.188 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
APNQ ARC QUENCHING METHOD DEION
CPRW ACTUATOR FUNCTION TRIP W/SEPARATE RESET
FEAT SPECIAL FEATURES MTG HOLES IRREGULARLY SPACED
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.164 INCHES
AXHR MOUNTING FACILITY TYPE AND QUANTITY 3 UNTHREADED HOLE
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
ABMK OVERALL WIDTH 3.500 INCHES NOMINAL
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 22.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 160.000 NOMINAL AT 125 PCT ALL LOCATIONS AND 5.000 NOMINAL AT 300 PCT ALL LOCATIONS
ABHP OVERALL LENGTH 6.500 INCHES NOMINAL

Similar Parts

451D852G06 , 451D852G06 , 5925-00-923-2118 , 5925009232118 , 009232118 , EH2070 , 451D852G06 ,