NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
ET1574E1A 30086 A 3 2 X XX

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CQQC TRIP RELEASE DUTY CYCLE CONTINUOUS ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.250 INCHES
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FEAT SPECIAL FEATURES FLUSH MTD ON 11.750 IN. BY 8.000 IN. MTG CENTERS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 40.0 AMPERES AC ALL LOCATIONS
ABMK OVERALL WIDTH 6.687 INCHES NOMINAL
AKPX POLE QUANTITY 3
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
ABKW OVERALL HEIGHT 9.625 INCHES NOMINAL
APNQ ARC QUENCHING METHOD DEION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 7500.0 AC ALL LOCATIONS
ADTV CASE MATERIAL METAL
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
ABHP OVERALL LENGTH 13.093 INCHES NOMINAL
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 3.000 MINIMUM AT 500 PCT ALL LOCATIONS AND 240.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 5.000 MAXIMUM AT 500 PCT ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 115.0 ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 PIN

Similar Parts

ET1574E1A , ET1574E1A , 5925-00-965-8497 , 5925009658497 , 009658497 , ET1574E1A ,