NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
454D507G04 | 89946 | A | 3 | 2 | 5 | TX |
CAGE Information
Code | Company |
---|---|
89946 | EATON CORPORATION |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION AND TIME DELAY SINGLE LOCATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC SINGLE LOCATION AND 125.0 DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION AND 2000.0 DC SINGLE LOCATION |
ADAQ | BODY LENGTH | 3.500 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
AJEC | BOSS HEIGHT | 0.188 INCHES NOMINAL |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 1 CLIP AND 1 COMPRESSION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION AND 20.0 AMPERES DC SINGLE LOCATION |
ADAU | BODY HEIGHT | 2.312 INCHES NOMINAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
ADAT | BODY WIDTH | 0.969 INCHES NOMINAL |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 TERMINAL |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 11.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 90.000 MAXIMUM AT 200 PCT SINGLE LOCATION |