NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
975052-1 | 49956 | A | 5 | 9 | A | TX | ||
975052-1 | 3B150 | A | 3 | 2 | A | TX | ||
CD3-Z230-1 | 74193 | H | 5 | 9 | 6 | TX |
CAGE Information
Code | Company |
---|---|
3B150 | RAYTHEON TECHNICAL SERVICES COMPANY |
49956 | RAYTHEON COMPANY DBA RAYTHEON |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCKPROOF |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE ONE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.200 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.700 MAXIMUM AT 200 PCT ALL LOCATIONS |
AKPX | POLE QUANTITY | 3 |
PKWT | UNPACKAGED UNIT WEIGHT | 2.250 POUNDS |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
ABTD | MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE AND 6 SLOT |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 2.5 AC AND 1.0 DC |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.032 INCHES NOMINAL |
CPRQ | RESET METHOD | MANUAL |
AJEC | BOSS HEIGHT | 0.218 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
THSD | THREAD SERIES DESIGNATOR | UNC |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.032 INCHES NOMINAL |
CRTK | SWITCH TERMINAL TYPE | TURRET |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.546 INCHES NOMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
ADAT | BODY WIDTH | 3.093 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.609 INCHES NOMINAL |
ADAQ | BODY LENGTH | 5.844 INCHES NOMINAL |
CMLP | THREAD QUANTITY PER INCH | 32 |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |