NIIN Output Data
NIIN:
NSN:
Item Name:
CIRCUIT BREAKER
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
CAGE Information
Code |
Company |
81541 |
SENSATA TECHNOLOGIES MARYLAND INC |
Characteristics (Decoded)
MRC |
Requirements Statement |
Clear Text Reply |
FREQ |
FREQUENCY IN HERTZ |
50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS |
AJEC |
BOSS HEIGHT |
0.150 INCHES NOMINAL |
AKPX |
POLE QUANTITY |
3 |
FEAT |
SPECIAL FEATURES |
1 HEX NUT 2 FLAT WASHERS PROVIDED WITH EACH TERM |
TTQY |
TERMINAL TYPE AND QUANTITY |
2 THREADED STUD |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
3 TOGGLE |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.060 INCHES NOMINAL |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT AND SALT SPRAY PROOF AND DUSTPROOF AND WATER RESISTANT |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
5000.0 AC ALL LOCATIONS |
CPRQ |
RESET METHOD |
AUTOMATIC |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
ADTV |
CASE MATERIAL |
PLASTIC |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 THREADED HOLE |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
480.0 AC ALL LOCATIONS |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
2.0 AMPERES AC ALL LOCATIONS |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
0.700 MINIMUM AT 125 PCT ALL LOCATIONS AND 10.000 MAXIMUM AT 125 PCT ALL LOCATIONS |
AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
ADAQ |
BODY LENGTH |
2.490 INCHES NOMINAL |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
Similar Parts