Follow Us on Google+

Request A Price Quote:

NIIN Output Data

NIIN:
NSN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
6010632-021 74193 H 5 9 5 TX
6010632-021 12436 A 3 2 A TX
299-4-5055-21 81541 A 5 2 6 TX

CAGE Information

Code Company
12436 BAE SYSTEMS NATIONAL SECURITY SOLUTI
74193 EATON CORP HEINEMANN PRODUCTS COMMER
81541 SENSATA TECHNOLOGIES MARYLAND INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 DC FOURTH LOCATION
FREQ FREQUENCY IN HERTZ 400.0 THIRD LOCATION
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC SECOND LOCATION
AKPX POLE QUANTITY 4
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 50.0 AMPERES AC THIRD LOCATION
ADAT BODY WIDTH 4.144 INCHES MAXIMUM
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 3.540 INCHES MINIMUM AND 3.560 INCHES MAXIMUM
ADAQ BODY LENGTH 4.740 INCHES MINIMUM AND 4.760 INCHES MAXIMUM
TTQY TERMINAL TYPE AND QUANTITY 8 THREADED STUD
AFJN FRAGILITY FACTOR MODERATELY RUGGED
AJEC BOSS HEIGHT 0.210 INCHES MINIMUM AND 0.230 INCHES MAXIMUM
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 4 TOGGLE
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 20.000 MINIMUM AT 200 PCT FIRST LOCATION AND 20.000 MINIMUM AT 200 PCT THIRD LOCATION AND 20.000 MINIMUM AT 200 PCT SECOND LOCATION AND 200.000 MAXIMUM AT 200 PCT FIRST LOCATION
FREQ FREQUENCY IN HERTZ 400.0 FIRST LOCATION
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 120.0 DC FOURTH LOCATION
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF AND FUNGUS PROOF
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 277.0 AC THIRD LOCATION
ADTV CASE MATERIAL PLASTIC
AXHR MOUNTING FACILITY TYPE AND QUANTITY 8 THREADED HOLE
CPRQ RESET METHOD MANUAL
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 200.000 MAXIMUM AT 200 PCT SECOND LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 50.0 AMPERES AC FIRST LOCATION
THSD THREAD SERIES DESIGNATOR UNC
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC THIRD LOCATION
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 200.000 MAXIMUM AT 200 PCT THIRD LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY FIRST LOCATION
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 3.540 INCHES MINIMUM AND 3.560 INCHES MAXIMUM
CPRW ACTUATOR FUNCTION TRIP-RESET
FREQ FREQUENCY IN HERTZ 400.0 SECOND LOCATION
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC FIRST LOCATION
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 277.0 AC FIRST LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS FOURTH LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SECOND LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 50.0 AMPERES AC SECOND LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 277.0 AC SECOND LOCATION
CMLP THREAD QUANTITY PER INCH 32
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY THIRD LOCATION
CQJX NOMINAL THREAD SIZE 0.138 INCHES

Similar Parts

6010632-021 , 6010632021 , 5925-01-259-7785 , 5925012597785 , 012597785 , 6010632-021 , 6010632-021 , 299-4-5055-21 ,