NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
MIL-C-39019/5 | 81349 | M | 4 | 1 | E | TX | ||
M39019/05-244 | 81349 | M | 2 | 2 | E | TX |
CAGE Information
Code | Company |
---|---|
81349 | MILITARY SPECIFICATIONS PROMULGATED |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS PROOF |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.828 INCHES MAXIMUM |
AEFP | NONTURN DEVICE RADIUS | 0.625 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
THSD | THREAD SERIES DESIGNATOR | UNEF |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
ABXD | BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS AND 500.0 DC ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 50.0 DC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 9.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
AEFS | NONTURN DEVICE DIAMETER | 0.250 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 8.0 AMPERES AC ALL LOCATIONS AND 8.0 AMPERES DC ALL LOCATIONS |
ADAT | BODY WIDTH | 1.937 INCHES MAXIMUM |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.594 INCHES MINIMUM AND 0.656 INCHES MAXIMUM |
ADTV | CASE MATERIAL | METAL |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-39019/5 GOVERNMENT SPECIFICATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-39019 SPECIFICATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
ADAQ | BODY LENGTH | 1.562 INCHES MAXIMUM |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
CMLP | THREAD QUANTITY PER INCH | 32 |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 6 WIRE HOOK |
AEFN | NONTURN DEVICE LOCATION | AT 3 OCLOCK AND AT 9 OCLOCK |