NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
JA2-K3K16Z84-32610A | 74193 | H | 5 | 9 | E | TX | ||
JA2-K3K16 | 74193 | H | C | 1 | 6 | ZZ | AC | |
65A1288 | 29192 | A | 3 | 2 | A | TX | ||
JA2-Z476-1 | 81118 | A | 5 | 2 | 5 | ZZ | ||
JA2-Z476-1 | 74193 | H | 5 | 9 | 5 | TX | ||
JA2-Z476-1W | 81118 | A | 5 | 2 | 5 | ZZ |
CAGE Information
Code | Company |
---|---|
29192 | OLYMPUS NDT NE INC. |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
81118 | EATON CORPORATION DBA FLUID POWER PL |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
TTQY | TERMINAL TYPE AND QUANTITY | 6 TAB, SOLDER LUG |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.898 INCHES MINIMUM AND 1.962 INCHES MAXIMUM |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
CPRK | AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 48.0 DC NOMINAL SECOND LOCATION |
AKPX | POLE QUANTITY | 2 |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES/RELAY TRIP SECOND LOCATION |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CQQC | TRIP RELEASE DUTY CYCLE | CONTINUOUS SECOND LOCATION |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.528 INCHES MINIMUM AND 1.592 INCHES MAXIMUM |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AJEC | BOSS HEIGHT | 0.098 INCHES MINIMUM AND 0.162 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
THSD | THREAD SERIES DESIGNATOR | UNC |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.628 INCHES MINIMUM AND 1.692 INCHES MAXIMUM |
ADAQ | BODY LENGTH | 1.968 INCHES MINIMUM AND 2.032 INCHES MAXIMUM |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ADAT | BODY WIDTH | 1.468 INCHES MINIMUM AND 1.532 INCHES MAXIMUM |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CMLP | THREAD QUANTITY PER INCH | 32 |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |