NIIN Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
STK2/4E-115A | 30086 | A | 3 | 2 | 5 | ZZ | ||
117588 | 30086 | A | D | 9 | A | ZZ |
CAGE Information
Code | Company |
---|---|
30086 | SPD ELECTRICAL SYSTEMS INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
AKPX | POLE QUANTITY | 3 |
BBRG | STORAGE TYPE | UNIMPROVED OPEN |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
ADAT | BODY WIDTH | 9.000 INCHES NOMINAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SHUNT TRIP ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
AJEC | BOSS HEIGHT | 0.188 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 115.0 AMPERES AC ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 3.000 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
THSD | THREAD SERIES DESIGNATOR | UNC |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 20000.0 AC ALL LOCATIONS |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 6.625 INCHES NOMINAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.875 INCHES NOMINAL |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED STUD |
ABKW | OVERALL HEIGHT | 10.156 INCHES NOMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |