Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
33322 GETRONICS GOVERNMENT SOLUTIONS LLC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC ALL LOCATIONS
FREQ FREQUENCY IN HERTZ 50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS
PRMT PRECIOUS MATERIAL SILVER
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 150.000 MAXIMUM AT 200 PCT ALL LOCATIONS
PMLC PRECIOUS MATERIAL AND LOCATION CONTACT SURFACES SILVER
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
ADAT BODY WIDTH 3.000 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 2.734 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED HOLE
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.000 INCHES NOMINAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 135.0 ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.000 INCHES NOMINAL
THSD THREAD SERIES DESIGNATOR UNC
ADAQ BODY LENGTH 4.031 INCHES MAXIMUM
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.250 INCHES NOMINAL
CPRW ACTUATOR FUNCTION TRIP-RESET
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
TTQY TERMINAL TYPE AND QUANTITY 6 SCREW
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
ADAU BODY HEIGHT 2.938 INCHES MAXIMUM
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CMLP THREAD QUANTITY PER INCH 32
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED GENERAL PURPOSE
CQJX NOMINAL THREAD SIZE 0.138 INCHES

Similar Parts

04770042-001 , 04770042001 , 5925-00-593-6407 , 5925005936407 , 005936407