Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
00742 | AIR PRODUCTS AND CHEMICALS INC. DBA |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AGAV | END ITEM IDENTIFICATION | 2320-01-442-1940,TRUCK,CBT,(COMMAND BRIDGE TRANSPORTER) |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION AND 50.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
AAQL | BODY STYLE | SINGLE POLE TYPE |
THSD | THREAD SERIES DESIGNATOR | UNEF |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION AND 2000.0 DC SINGLE LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SINGLE LOCATION AND 5.0 AMPERES DC SINGLE LOCATION |
CMLP | THREAD QUANTITY PER INCH | 28 |
ABXD | BUSHING LENGTH | 0.300 INCHES NOMINAL |
ADAT | BODY WIDTH | 0.660 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.850 INCHES NOMINAL |
CQJX | NOMINAL THREAD SIZE | 0.438 INCHES |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.815 INCHES NOMINAL |
ADAQ | BODY LENGTH | 1.375 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | RESET |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
PKWT | UNPACKAGED UNIT WEIGHT | 1.500 OUNCES |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 6.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 30.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCKPROOF AND VIBRATIONPROOF |
TTQY | TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |