Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
81541 | SENSATA TECHNOLOGIES MARYLAND INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
FREQ | FREQUENCY IN HERTZ | 50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
AKPX | POLE QUANTITY | 2 |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
PKWT | UNPACKAGED UNIT WEIGHT | 7.400 OUNCES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.180 MINIMUM AT 200 PCT ALL LOCATIONS AND 1.800 MAXIMUM AT 200 PCT ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.625 INCHES MAXIMUM |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
CPRQ | RESET METHOD | MANUAL |
FEAT | SPECIAL FEATURES | BLACK HANDLE |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM |
THSD | THREAD SERIES DESIGNATOR | UNC |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ADAQ | BODY LENGTH | 2.480 INCHES MINIMUM AND 2.500 INCHES MAXIMUM |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTTIGHT AND HERMETICALLY SEALED |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADTV | CASE MATERIAL | METAL |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
ADAT | BODY WIDTH | 1.515 INCHES MAXIMUM |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CMLP | THREAD QUANTITY PER INCH | 32 |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |