Part Number
Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code |
Company |
81541 |
SENSATA TECHNOLOGIES MARYLAND INC |
Characteristics (Decoded)
MRC |
Requirements Statement |
Clear Text Reply |
FREQ |
FREQUENCY IN HERTZ |
50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS |
AKPX |
POLE QUANTITY |
3 |
CPRJ |
TRIP RELEASE METHOD |
SOLID STATE ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
3 TOGGLE |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
6 UNTHREADED HOLE |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.060 INCHES NOMINAL |
AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.156 INCHES NOMINAL |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
5000.0 AC ALL LOCATIONS |
ADAT |
BODY WIDTH |
2.265 INCHES MAXIMUM |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
0.150 MINIMUM AT 200 PCT ALL LOCATIONS AND 1.500 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRQ |
RESET METHOD |
MANUAL |
CPRW |
ACTUATOR FUNCTION |
RESET |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
12.0 AMPERES AC ALL LOCATIONS |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.750 INCHES NOMINAL |