Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
06424 | ALLIANT TECHSYSTEMS INC. DIV DEFENSE |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
FREQ | FREQUENCY IN HERTZ | 50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AKPX | POLE QUANTITY | 3 |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
ADAT | BODY WIDTH | 2.265 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
PKWT | UNPACKAGED UNIT WEIGHT | 11.100 OUNCES |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.475 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 3.0 DC |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
CRTK | SWITCH TERMINAL TYPE | QUICK DISCONNECT, MALE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES AC ALL LOCATIONS |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM |
THSD | THREAD SERIES DESIGNATOR | UNC |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ADAQ | BODY LENGTH | 2.480 INCHES MINIMUM AND 2.500 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
AAJE | THREAD PITCH DIAMETERS | +0.1177/+0.1214 INCHES |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |