AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
FREQ |
FREQUENCY IN HERTZ |
60.0 SINGLE LOCATION |
BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SINGLE LOCATION |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
125.0 AC SINGLE LOCATION |
CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
1 ALARM |
AAQL |
BODY STYLE |
SINGLE POLE TYPE |
CSWP |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS |
250.0 AC AND 50.0 DC |
AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
TTQY |
TERMINAL TYPE AND QUANTITY |
2 THREADED STUD |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP SINGLE LOCATION |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
1.000 MINIMUM SINGLE LOCATION AND 6.000 MAXIMUM SINGLE LOCATION |
ADAT |
BODY WIDTH |
0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
2.0 AMPERES AC SINGLE LOCATION |
AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
CSSX |
SWITCH CURRENT RATING AND TYPE IN AMPS |
2.5 AC AND 1.0 DC |
CQSM |
SWITCH LOCATION AND POSITION DESIGNATION |
INTERNAL AT POLE ONE |
ADTV |
CASE MATERIAL |
PLASTIC |
AKPX |
POLE QUANTITY |
1 |
CPRQ |
RESET METHOD |
MANUAL |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
0.850 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.090 MINIMUM AT 300 PCT SINGLE LOCATION AND 0.250 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.280 MAXIMUM AT 300 PCT SINGLE LOCATION |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 THREADED HOLE |
THSD |
THREAD SERIES DESIGNATOR |
UNC |
CRTK |
SWITCH TERMINAL TYPE |
TAB, SOLDER LUG |
AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
ADAQ |
BODY LENGTH |
2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE ONE |
AJEC |
BOSS HEIGHT |
0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY SINGLE LOCATION |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
2000.0 AC SINGLE LOCATION |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 SINGLE LOCATION |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |