Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
H0203 THALES NEDERLAND

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS AND 0.055 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.240 MAXIMUM AT 400 PCT ALL LOCATIONS
ADAT BODY WIDTH 1.281 INCHES MAXIMUM
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.828 INCHES MAXIMUM
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 500.0 MILLIAMPERES AC ALL LOCATIONS AND 500.0 MILLIAMPERES DC ALL LOCATIONS
ABXD BUSHING LENGTH 0.380 INCHES MAXIMUM
CPRZ AUXILIARY SWITCH FUNCTION AND QUANTITY 1 ALARM
AKPX POLE QUANTITY 2
THSD THREAD SERIES DESIGNATOR UNEF
CPRX ACTUATOR POSITION DESIGNATION BETWEEN POLE ONE AND TWO
TEST TEST DATA DOCUMENT 81349-MIL-PRF-39019 SPECIFICATION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 300.0 AC ALL LOCATIONS AND 500.0 DC ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY THD BUSHING W/PANEL SEAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CQJX NOMINAL THREAD SIZE 0.375 INCHES
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS AND 50.0 DC ALL LOCATIONS
AEGJ SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT
CPRQ RESET METHOD MANUAL
CSWP SWITCH VOLTAGE RATING AND TYPE IN VOLTS 120.0 AC AND 50.0 DC
TTQY TERMINAL TYPE AND QUANTITY 4 WIRE HOOK
CPRJ TRIP RELEASE METHOD MAGNETIC ALL LOCATIONS
CRTK SWITCH TERMINAL TYPE TAB, SOLDER LUG
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
CQSM SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE TWO
ADTV CASE MATERIAL METAL
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.625 INCHES NOMINAL
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ADAQ BODY LENGTH 1.562 INCHES MAXIMUM
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE AND TWO LINKED
CMLP THREAD QUANTITY PER INCH 32
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.906 INCHES MAXIMUM
ZZZK SPECIFICATION/STANDARD DATA 81349-MIL-PRF-39019/4 GOVERNMENT SPECIFICATION
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 0.200 MINIMUM ALL LOCATIONS AND 7.000 MAXIMUM ALL LOCATIONS