Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
53711 | NAVAL SEA SYSTEMS COMMAND |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
ADAT | BODY WIDTH | 1.281 INCHES MAXIMUM |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS OR 400.0 ALL LOCATIONS |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
AKPX | POLE QUANTITY | 2 |
THSD | THREAD SERIES DESIGNATOR | UNEF |
AGAV | END ITEM IDENTIFICATION | WEAPON LAUNCH CONSOL ASSEMBLY FOR LOS ANGELES CLASS SUBMARINE 688 |
ABXD | BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-39019 SPECIFICATION SPECIFICATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS AND 500.0 DC ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 50.0 DC ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
CPRQ | RESET METHOD | MANUAL |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 23.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 27.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.625 INCHES NOMINAL |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 800.0 ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND CORROSION RESISTANT AND HERMETICALLY SEALED |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.906 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.950 INCHES MAXIMUM |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-39019/4 GOVERNMENT SPECIFICATION |
ADTV | CASE MATERIAL | METAL |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.240 MAXIMUM AT 400 PCT ALL LOCATIONS AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS AND 0.055 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.060 MAXIMUM AT 800 PCT ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
ADAQ | BODY LENGTH | 1.562 INCHES MAXIMUM |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CMLP | THREAD QUANTITY PER INCH | 32 |
AEGJ | SWITCH CONTACT ARRANGEMENT | DOUBLE POLE, SINGLE THROW, NORMALLY CLOSED |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 0.720 INCHES MINIMUM AND 0.780 INCHES MAXIMUM |