Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
79500 | WESTINGHOUSE ELECTRIC CORP |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 DC ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 ALL LOCATIONS |
AKPX | POLE QUANTITY | 2 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES DC ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 DC ALL LOCATIONS |
ABHP | OVERALL LENGTH | 10.000 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 8.750 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.625 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | RESET |
APNQ | ARC QUENCHING METHOD | DEION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ABMK | OVERALL WIDTH | 5.000 INCHES NOMINAL |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 240.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 7.500 MAXIMUM AT 300 PCT ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ABKW | OVERALL HEIGHT | 4.750 INCHES NOMINAL |