Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
74193 EATON CORP HEINEMANN PRODUCTS COMMER

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 40.0 AMPERES AC ALL LOCATIONS
AKPX POLE QUANTITY 3
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1500.0 AC ALL LOCATIONS
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 70.000 NOMINAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 3.310 INCHES MAXIMUM
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 3.050 INCHES MINIMUM AND 3.070 INCHES MAXIMUM
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
ADAT BODY WIDTH 3.060 INCHES MAXIMUM
THSD THREAD SERIES DESIGNATOR UNC
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
AJEC BOSS HEIGHT 0.145 INCHES MINIMUM AND 0.175 INCHES MAXIMUM
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 2.040 INCHES MINIMUM AND 2.080 INCHES MAXIMUM
TTQY TERMINAL TYPE AND QUANTITY 6 THREADED STUD
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
ADAQ BODY LENGTH 3.790 INCHES MAXIMUM
CMLP THREAD QUANTITY PER INCH 32
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 2.060 INCHES NOMINAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 416.0 AC ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 8.000 NOMINAL AT 400 PCT ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.138 INCHES