Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
AP112-12HRR 81541 A 3 2 6 TX
128C099H08 97942 A 7 2 A TX
SM333HHK7-5-240VAC400C1 74193 H 5 9 E TX

CAGE Information

Code Company
74193 EATON CORP HEINEMANN PRODUCTS COMMER
81541 SENSATA TECHNOLOGIES MARYLAND INC
97942 NORTHROP GRUMMAN SYSTEMS CORPORATION

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CSWP SWITCH VOLTAGE RATING AND TYPE IN VOLTS 125.0 AC AND 50.0 DC
CSWP SWITCH VOLTAGE RATING AND TYPE IN VOLTS 125.0 AC AND 50.0 DC
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 3.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 15.000 MAXIMUM AT 150 PCT ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CSSX SWITCH CURRENT RATING AND TYPE IN AMPS 1.0 AC AND 0.5 DC
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 6.5000 MINIMUM ALL LOCATIONS AND 30.000 MAXIMUM ALL LOCATIONS
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.678 INCHES NOMINAL
THSD THREAD SERIES DESIGNATOR UNEF
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 7.5 AMPERES AC ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 300.0 AC ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CQJX NOMINAL THREAD SIZE 0.375 INCHES
TEST TEST DATA DOCUMENT 97942-128C099 DRAWING
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
AAJE THREAD PITCH DIAMETERS +0.3503/+0.3537 INCHES
AEGJ SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
CPRZ AUXILIARY SWITCH FUNCTION AND QUANTITY 2 CONTROL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
CPRQ RESET METHOD MANUAL
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.875 INCHES NOMINAL
ADAQ BODY LENGTH 1.495 INCHES NOMINAL
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
ADAT BODY WIDTH 1.872 INCHES NOMINAL
CRTK SWITCH TERMINAL TYPE TAB, SOLDER LUG
ABXD BUSHING LENGTH 0.375 INCHES NOMINAL
CPRW ACTUATOR FUNCTION TRIP-RESET
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED HERMETICALLY SEALED
ADTV CASE MATERIAL METAL
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.625 INCHES NOMINAL
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CMLP THREAD QUANTITY PER INCH 32
TTQY TERMINAL TYPE AND QUANTITY 6 WIRE HOOK
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 115.0 ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 3 THREADED BUSHING

Similar Parts

SM333HHK7-5-240VAC400C1 , SM333HHK75240VAC400C1 , 5925-00-054-0402 , 5925000540402 , 000540402 , AP112-12HRR , 128C099H08 , SM333HHK7-5-240VAC400C1 ,