National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
711518-10 | 05869 | A | C | 1 | 5 | TX | AF | |
711518-010 | 05869 | A | C | 1 | 6 | ZZ | AC | |
AM3-2353-10 | 74193 | H | C | 1 | E | TX | AF | |
M55629/6-061 | 81349 | M | 2 | 2 | E | TX | ||
MIL-PRF-55629/6 | 81349 | M | 4 | 1 | E | ZZ | ||
72-327-10MG6 | 74193 | H | C | 1 | 5 | TX | AF | |
APL-111-1RO-1971-10 | 81541 | A | C | 1 | 5 | TX | AF | |
MIL-C-55629/6 | 81349 | M | 5 | 9 | E | TX |
CAGE Information
Code | Company |
---|---|
05869 | RAYTHEON COMPANY DBA RAYTHEON |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
81349 | MILITARY SPECIFICATIONS PROMULGATED |
81541 | SENSATA TECHNOLOGIES MARYLAND INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.800 INCHES MAXIMUM |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AKPX | POLE QUANTITY | 3 |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
ADAT | BODY WIDTH | 2.205 INCHES MINIMUM AND 2.285 INCHES MAXIMUM |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 2.0 DC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.046 INCHES MINIMUM AND 2.078 INCHES MAXIMUM |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
CPRQ | RESET METHOD | MANUAL |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/6 GOVERNMENT SPECIFICATION |
THSD | THREAD SERIES DESIGNATOR | UNC |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.160 MINIMUM AT 200 PCT ALL LOCATIONS AND 1.600 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.0 AMPERES AC ALL LOCATIONS |
ADAQ | BODY LENGTH | 2.510 INCHES MAXIMUM |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND CORROSION RESISTANT AND FUNGUS RESISTANT AND VIBRATION RESISTANT |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.661 INCHES MINIMUM AND 1.960 INCHES MAXIMUM |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
PKWT | UNPACKAGED UNIT WEIGHT | 0.625 POUNDS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
CMLP | THREAD QUANTITY PER INCH | 32 |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |