Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
KAB36150 56302 A 3 2 E TX
KAB36150 56365 A 5 9 E TX

CAGE Information

Code Company
56302 SQUARE D CO CEDAR RAPIDS MFG PLANT
56365 SCHNEIDER ELECTRIC USA INC. DBA SCHN

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 138.0 ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ADAT BODY WIDTH 4.500 INCHES NOMINAL
ADAQ BODY LENGTH 8.000 INCHES NOMINAL
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 25000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 TERMINAL
FEAT SPECIAL FEATURES WITH BOLT-ON BRACKET CONNECTION
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.500 INCHES NOMINAL
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 150.0 AMPERES AC ALL LOCATIONS AND 150.0 AMPERES DC ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
AJEC BOSS HEIGHT 0.156 INCHES NOMINAL
ADAU BODY HEIGHT 4.500 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
TTQY TERMINAL TYPE AND QUANTITY 3 CLIP AND 3 COMPRESSION
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CRCF TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 150.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 250.000 MAXIMUM AT 200 PCT ALL LOCATIONS

Similar Parts

KAB36150 , KAB36150 , 5925-00-405-1209 , 5925004051209 , 004051209 , KAB36150 , KAB36150 ,