Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
ET72090 30086 A 3 2 X XX
9022018 18876 A 5 2 X XX

CAGE Information

Code Company
18876 U S ARMY AVIATION AND MISSILE COMMAN
30086 SPD ELECTRICAL SYSTEMS INC

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 70.0 AMPERES AC ALL LOCATIONS AND 70.0 AMPERES DC ALL LOCATIONS
AKPX POLE QUANTITY 3
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED STUD
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 110.0 ALL LOCATIONS
CPRQ RESET METHOD MANUAL
THSD THREAD SERIES DESIGNATOR UNC
CPRW ACTUATOR FUNCTION TRIP-RESET
CQJX NOMINAL THREAD SIZE 0.164 INCHES
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 32
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 240.000 NOMINAL AT 150 PCT ALL LOCATIONS AND 60.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 20.000 NOMINAL AT 300 PCT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 PIN

Similar Parts

9022018 , 9022018 , 5925-00-729-7750 , 5925007297750 , 007297750 , ET72090 , 9022018 ,