National Stock Number (NSN) Output Data
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number |
CAGE |
Status |
RNCC |
RNVC |
DAC |
RNAAC |
MSDS |
SADC |
ET72090 |
30086 |
A |
3 |
2 |
X |
XX |
|
|
9022018 |
18876 |
A |
5 |
2 |
X |
XX |
|
|
CAGE Information
Code |
Company |
18876 |
U S ARMY AVIATION AND MISSILE COMMAN |
30086 |
SPD ELECTRICAL SYSTEMS INC |
Characteristics (Decoded)
MRC |
Requirements Statement |
Clear Text Reply |
CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
70.0 AMPERES AC ALL LOCATIONS AND 70.0 AMPERES DC ALL LOCATIONS |
AKPX |
POLE QUANTITY |
3 |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED STUD |
CPRJ |
TRIP RELEASE METHOD |
THERMAL ALL LOCATIONS |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
ADTV |
CASE MATERIAL |
PLASTIC |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
110.0 ALL LOCATIONS |
CPRQ |
RESET METHOD |
MANUAL |
THSD |
THREAD SERIES DESIGNATOR |
UNC |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CQJX |
NOMINAL THREAD SIZE |
0.164 INCHES |
CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
240.000 NOMINAL AT 150 PCT ALL LOCATIONS AND 60.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 20.000 NOMINAL AT 300 PCT ALL LOCATIONS |
TTQY |
TERMINAL TYPE AND QUANTITY |
6 PIN |
Similar Parts