National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
483120-4 | 3B150 | A | 5 | 2 | A | TX | ||
483120-4 | 49956 | A | 5 | 9 | A | TX | ||
AM12MG6-7-5-50VDC5 | 74193 | H | 3 | 9 | E | TX | ||
4MC2-7-7-5 | 82647 | A | 5 | 2 | E | TX |
CAGE Information
Code | Company |
---|---|
3B150 | RAYTHEON TECHNICAL SERVICES COMPANY |
49956 | RAYTHEON COMPANY DBA RAYTHEON |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
82647 | SENSATA TECHNOLOGIES INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.471 INCHES NOMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.350 MINIMUM AT 150 PCT SINGLE LOCATION AND 0.170 MINIMUM AT 200 PCT SINGLE LOCATION AND 1.500 MAXIMUM AT 150 PCT SINGLE LOCATION AND 0.060 MINIMUM AT 300 PCT SINGLE LOCATION AND 0.500 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.200 MAXIMUM AT 300 PCT SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
CPRQ | RESET METHOD | MANUAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
THSD | THREAD SERIES DESIGNATOR | UNC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND FUNGUS RESISTANT AND EXPLOSION RESISTANT |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.700 MINIMUM SINGLE LOCATION AND 2.800 MAXIMUM SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.5 AMPERES DC SINGLE LOCATION |