National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
625030-3 | 96046 | A | 3 | 2 | 5 | HD |
CAGE Information
Code | Company |
---|---|
96046 | CRANE PUMPS & SYSTEMS INC. |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
ADAT | BODY WIDTH | 4.500 INCHES NOMINAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 19.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ADAQ | BODY LENGTH | 5.250 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.359 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 12 UNTHREADED HOLE |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.000 INCHES NOMINAL |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AJEC | BOSS HEIGHT | 0.219 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.359 INCHES NOMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
ADAU | BODY HEIGHT | 2.688 INCHES NOMINAL |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |