Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
6415857 001JK A 5 9 4 ZF
6415857 S4956 R 5 9 4 9Z
7274-4-10 82647 A C 1 4 TX AF
MIL-C-5809 81349 M 4 1 E TX
MS26574-10A 96906 M 2 2 E TX
Q531487060 S3092 A 5 9 3 9Z

CAGE Information

Code Company
001JK EMBRAER S/A
S4956 EMBRAER EMPRESA BRASILEIRA DE AERONA
82647 SENSATA TECHNOLOGIES INC
81349 MILITARY SPECIFICATIONS PROMULGATED
96906 MILITARY STANDARDS PROMULGATED BY MI
S3092 RHEINMETALL AIR DEFENCE AG

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 20.000 MAXIMUM AT 200 PCT SINGLE LOCATION
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC SINGLE LOCATION AND 10.0 AMPERES DC SINGLE LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 1 THREADED BUSHING
CPRZ AUXILIARY SWITCH FUNCTION AND QUANTITY 1 ALARM
AAQL BODY STYLE SINGLE POLE TYPE
AFJN FRAGILITY FACTOR MODERATELY RUGGED
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.420 INCHES MAXIMUM
THSD THREAD SERIES DESIGNATOR UN
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
TTQY TERMINAL TYPE AND QUANTITY 2 TAB W/SCREW
CSWP SWITCH VOLTAGE RATING AND TYPE IN VOLTS 200.0 AC AND 28.0 DC
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CQJX NOMINAL THREAD SIZE 0.438 INCHES
AEGJ SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS MAXIMUM SINGLE LOCATION
ABXD BUSHING LENGTH 0.359 INCHES NOMINAL
CQSM SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE ONE
ZZZK SPECIFICATION/STANDARD DATA 96906-MS26574 GOVERNMENT STANDARD
ADTV CASE MATERIAL PLASTIC
AKPX POLE QUANTITY 1
CPRQ RESET METHOD MANUAL
ADAT BODY WIDTH 0.580 INCHES MAXIMUM
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.593 INCHES NOMINAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 145.0 SINGLE LOCATION
ADAQ BODY LENGTH 0.780 INCHES MAXIMUM
CPRJ TRIP RELEASE METHOD THERMAL SINGLE LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 200.0 AC SINGLE LOCATION AND 28.0 DC SINGLE LOCATION
CRTK SWITCH TERMINAL TYPE TAB, SOLDER LUG
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 PUSH-PULL
CPRW ACTUATOR FUNCTION TRIP-RESET
TEST TEST DATA DOCUMENT 81349-MIL-C-5809 SPECIFICATION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 500.0 AC SINGLE LOCATION AND 500.0 DC SINGLE LOCATION
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE
FREQ FREQUENCY IN HERTZ 400.0 SINGLE LOCATION
CSSX SWITCH CURRENT RATING AND TYPE IN AMPS 3.0 AC AND 5.0 DC
CMLP THREAD QUANTITY PER INCH 32
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION

Similar Parts

6415857 , 6415857 , 5925-00-879-9402 , 5925008799402 , 008799402 , 6415857 , 6415857 , 7274-4-10 , MIL-C-5809 , MS26574-10A , Q531487060 ,