National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
6010632-021 | 74193 | H | 5 | 9 | 5 | TX | ||
6010632-021 | 12436 | A | 3 | 2 | A | TX | ||
299-4-5055-21 | 81541 | A | 5 | 2 | 6 | TX |
CAGE Information
Code | Company |
---|---|
12436 | BAE SYSTEMS NATIONAL SECURITY SOLUTI |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
81541 | SENSATA TECHNOLOGIES MARYLAND INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC FOURTH LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 THIRD LOCATION |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SECOND LOCATION |
AKPX | POLE QUANTITY | 4 |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC THIRD LOCATION |
ADAT | BODY WIDTH | 4.144 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.540 INCHES MINIMUM AND 3.560 INCHES MAXIMUM |
ADAQ | BODY LENGTH | 4.740 INCHES MINIMUM AND 4.760 INCHES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.210 INCHES MINIMUM AND 0.230 INCHES MAXIMUM |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT FIRST LOCATION AND 20.000 MINIMUM AT 200 PCT THIRD LOCATION AND 20.000 MINIMUM AT 200 PCT SECOND LOCATION AND 200.000 MAXIMUM AT 200 PCT FIRST LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 FIRST LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 DC FOURTH LOCATION |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC THIRD LOCATION |
ADTV | CASE MATERIAL | PLASTIC |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
CPRQ | RESET METHOD | MANUAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 200.000 MAXIMUM AT 200 PCT SECOND LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC FIRST LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNC |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC THIRD LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 200.000 MAXIMUM AT 200 PCT THIRD LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.540 INCHES MINIMUM AND 3.560 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
FREQ | FREQUENCY IN HERTZ | 400.0 SECOND LOCATION |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC FIRST LOCATION |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC FIRST LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS FOURTH LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SECOND LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC SECOND LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC SECOND LOCATION |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY THIRD LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |