Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
M39019/01-249S 81349 M 2 2 E 9Z
MIL-PRF-39019/1 81349 M 4 1 E 9Z

CAGE Information

Code Company
81349 MILITARY SPECIFICATIONS PROMULGATED

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC SINGLE LOCATION AND 50.0 DC SINGLE LOCATION
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED MOISTURE RESISTANT AND CORROSION RESISTANT AND FUNGUS RESISTANT AND WATER RESISTANT
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC SINGLE LOCATION AND 10.0 AMPERES DC SINGLE LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 1 THREADED BUSHING
AAQL BODY STYLE SINGLE POLE TYPE
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION OR 400.0 SINGLE LOCATION
THSD THREAD SERIES DESIGNATOR UNEF
ABXD BUSHING LENGTH 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM
AGAV END ITEM IDENTIFICATION TACTICAL AIR DEFENSE RADAR SYSTEM (TADRS)
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.500 MINIMUM AT 200 PCT SINGLE LOCATION AND 9.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TTQY TERMINAL TYPE AND QUANTITY 2 TAB W/SCREW
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CQJX NOMINAL THREAD SIZE 0.375 INCHES
CPRJ TRIP RELEASE METHOD MAGNETIC SINGLE LOCATION
PKWT UNPACKAGED UNIT WEIGHT 50.000 GRAMS
CTTC THREAD TOLERANCE CLASS 2A EXTERNAL
AKPX POLE QUANTITY 1
CPRQ RESET METHOD MANUAL
FEAT SPECIAL FEATURES MOUNTING BUSHING HAS ON-OFF IDENTIFICATION PLATE; MOUNTING BUSHING HAS KEYWAY 0.058 TO 0.068 INCH WIDTH BY 0.025 TO 0.035 INCH DEPTH
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.810 INCHES MAXIMUM
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 135.0 SINGLE LOCATION
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ADAQ BODY LENGTH 1.562 INCHES MAXIMUM
CMLP THREAD QUANTITY PER INCH 32
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
ADAT BODY WIDTH 0.625 INCHES MAXIMUM
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.906 INCHES MAXIMUM

Similar Parts

M39019/01-249S , M3901901249S , 5925-01-534-3129 , 5925015343129 , 015343129 , M39019/01-249S , MIL-PRF-39019/1 ,