National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
E2010V | 79500 | A | 5 | 9 | E | TX | ||
1532411 | 79500 | A | 5 | 2 | 5 | HD | ||
EB2010V | 11660 | H | 3 | 9 | E | TX |
CAGE Information
Code | Company |
---|---|
11660 | WESTINGHOUSE ELECTRIC CORP CONTROL B |
79500 | WESTINGHOUSE ELECTRIC CORP |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 26.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC ALL LOCATIONS AND 10.0 AMPERES DC ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.062 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
PKWT | UNPACKAGED UNIT WEIGHT | 3.000 POUNDS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.375 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND GENERAL PURPOSE AND FUNGUS RESISTANT |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.500 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
ABXD | BUSHING LENGTH | 0.125 INCHES NOMINAL |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |