Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
TRIPPER , CIRCUIT BREAKER

Definition:

AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
S1332231 79500 A 3 2 3 TX
K2175T 89946 A 5 2 3 TX

CAGE Information

Code Company
79500 WESTINGHOUSE ELECTRIC CORP
89946 EATON CORPORATION

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPSF ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS +500.0/+1750.0 AC ALL LOCATIONS AND +500.0/+1750.0 DC ALL LOCATIONS
AKPX POLE QUANTITY 2
ABKW OVERALL HEIGHT 3.250 INCHES NOMINAL
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 175.0 AMPERES AC ALL LOCATIONS AND 175.0 AMPERES DC ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 4 COMPRESSION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 108.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 500.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CBBL FEATURES PROVIDED ADJUSTABLE TRIP RELEASE
AAQL BODY STYLE RECTANGULAR DIMENSIONAL ENVELOPE
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 122.0 ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
ABHP OVERALL LENGTH 4.750 INCHES NOMINAL
ABMK OVERALL WIDTH 3.750 INCHES NOMINAL
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 TERMINAL

Similar Parts

S1332231 , S1332231 , 5925-00-270-5986 , 5925002705986 , 002705986 , S1332231 , K2175T ,