Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
B27790 0BXF1 A 5 2 5 ZZ
7900042-016 24617 A 5 2 5 TX
201570 01359 A 3 2 5 TX
B27790 07860 R 5 9 5 TX
AM333MG615A 74193 H 5 9 5 9Z
AM333MG6-15 74193 H 5 9 E TX
AM333MG6-15-125-14-400 74193 H 5 9 E TX

CAGE Information

Code Company
01359 FAIRCHILD CONTROLS CORPORATION
0BXF1 BOGUE SYSTEMS INC.
24617 GENERAL MOTORS CORP
07860 BOGUE ELECTRIC MANUFACTURING CO
74193 EATON CORP HEINEMANN PRODUCTS COMMER

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES AC ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
AKPX POLE QUANTITY 3
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1500.0 AC ALL LOCATIONS
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.750 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
ADAT BODY WIDTH 2.250 INCHES NOMINAL
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.063 INCHES NOMINAL
ADAQ BODY LENGTH 2.500 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
AJEC BOSS HEIGHT 0.140 INCHES NOMINAL
CPRQ RESET METHOD MANUAL
THSD THREAD SERIES DESIGNATOR UNC
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.938 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 125.0 AC ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 29.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 90.000 MAXIMUM AT 200 PCT ALL LOCATIONS
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 THREADED STUD
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 32
CQJX NOMINAL THREAD SIZE 0.138 INCHES
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.750 INCHES NOMINAL
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.611 INCHES NOMINAL

Similar Parts