National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
W91X11-3-10 | 77342 | A | 3 | 2 | E | TX | ||
804785-11 | 96214 | A | 7 | 2 | 2 | 9Z | ||
AM1-A3-A-10-3 | 74193 | H | 5 | 9 | E | TX |
CAGE Information
Code | Company |
---|---|
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
77342 | TYCO ELECTRONICS CORPORATION |
96214 | RAYTHEON COMPANY |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
FREQ | FREQUENCY IN HERTZ | 50.0 SINGLE LOCATION OR 60.0 SINGLE LOCATION |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
ADAT | BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.030 MINIMUM AT 400 PCT SINGLE LOCATION AND 1.500 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.200 MAXIMUM AT 400 PCT SINGLE LOCATION |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
THSD | THREAD SERIES DESIGNATOR | UNC |
ADAQ | BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.700 MINIMUM SINGLE LOCATION |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
AJEC | BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL |