Follow Us on Google+

Request A Price Quote:

National Stock Number (NSN) Output Data

NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

Reference/Part Number

Part Number CAGE Status RNCC RNVC DAC RNAAC MSDS SADC
219-4-20141-1 81541 A 5 2 5 TX
5050213-1 57958 F 3 9 A TX
CD4-Z132-1 74193 H 5 9 6 TX

CAGE Information

Code Company
57958 SIGNALS WARFARE PROJECT MANAGER
81541 SENSATA TECHNOLOGIES MARYLAND INC
74193 EATON CORP HEINEMANN PRODUCTS COMMER

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
ADAT BODY WIDTH 4.128 INCHES NOMINAL
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
PKWT UNPACKAGED UNIT WEIGHT 2.700 POUNDS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 115.0 DC FOURTH LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SECOND LOCATION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 20.000 MINIMUM AT 200 PCT SECOND LOCATION AND 100.000 MAXIMUM AT 200 PCT SECOND LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 SECOND LOCATION
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC SECOND LOCATION
AKPX POLE QUANTITY 4
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 100.0 AMPERES AC FIRST LOCATION
CPRH CIRCUIT PROTECTION TYPE UNDERVOLTAGE FOURTH LOCATION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 20.000 MINIMUM AT 200 PCT FIRST LOCATION AND 100.000 MAXIMUM AT 200 PCT FIRST LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT THIRD LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC SECOND LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 THIRD LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 100.0 AMPERES AC SECOND LOCATION
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP FIRST LOCATION
TTQY TERMINAL TYPE AND QUANTITY 8 THREADED STUD
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC THIRD LOCATION
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SECOND LOCATION
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 4 TOGGLE
ABTD MOUNTING SLOT WIDTH 0.164 INCHES NOMINAL
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP THIRD LOCATION
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, THREE, AND FOUR LINKED
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 100.0 AMPERES AC THIRD LOCATION
CPSM INTERNAL TRIP RELEASE CONFIGURATION SHUNT TRIP FOURTH LOCATION
ADTV CASE MATERIAL PLASTIC
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.032 INCHES NOMINAL
CPRQ RESET METHOD MANUAL
AJEC BOSS HEIGHT 0.218 INCHES NOMINAL
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.750 INCHES NOMINAL
THSD THREAD SERIES DESIGNATOR UNC
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC THIRD LOCATION
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC FIRST LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY FIRST LOCATION
CPRW ACTUATOR FUNCTION TRIP-RESET
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.032 INCHES NOMINAL
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 20.000 MINIMUM AT 200 PCT THIRD LOCATION AND 100.000 MAXIMUM AT 200 PCT THIRD LOCATION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC FIRST LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 8 THREADED HOLE AND 8 SLOT
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 3.546 INCHES NOMINAL
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.609 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS FOURTH LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SECOND LOCATION
ADAQ BODY LENGTH 5.844 INCHES NOMINAL
CMLP THREAD QUANTITY PER INCH 32
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT FIRST LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 FIRST LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY THIRD LOCATION
CQJX NOMINAL THREAD SIZE 0.138 INCHES

Similar Parts

5050213-1 , 50502131 , 5925-01-161-9560 , 5925011619560 , 011619560 , 219-4-20141-1 , 5050213-1 , CD4-Z132-1 ,