National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
KS-20684L8 | 74193 | H | 5 | 9 | 5 | TX | ||
KS-20684L8 | 06KW9 | R | 3 | 2 | 5 | ZZ | ||
KS-20684L8 | 64959 | R | 5 | 9 | A | TX |
CAGE Information
Code | Company |
---|---|
06KW9 | LUCENT TECHNOLOGIES INC DBA FEDERAL |
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
64959 | AMERICAN TELEPHONE AND TELEGRAPH CO |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.295 INCHES NOMINAL |
ADAT | BODY WIDTH | 1.500 INCHES NOMINAL |
PRMT | PRECIOUS MATERIAL | SILVER |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE TWO |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
AKPX | POLE QUANTITY | 2 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES DC SECOND LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 65.0 DC ALL LOCATIONS |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES DC FIRST LOCATION |
PMLC | PRECIOUS MATERIAL AND LOCATION | CONTACT SURFACE SILVER |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
CPRQ | RESET METHOD | MANUAL |
THSD | THREAD SERIES DESIGNATOR | UNC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CRTK | SWITCH TERMINAL TYPE | TURRET |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 DC ALL LOCATIONS |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.175 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.400 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |