National Stock Number (NSN) Output Data
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
JE3S-N3-DR-01-D-50-2 | 74193 | H | 5 | 9 | E | TX | ||
JE3S-N3-DA-01-D-A-50-2 | 74193 | H | 3 | 9 | E | ZZ |
CAGE Information
Code | Company |
---|---|
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
AKPX | POLE QUANTITY | 3 |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SALT WATER RESISTANT AND SHOCK RESISTANT AND MOISTURE RESISTANT AND VIBRATION RESISTANT |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CQJX | NOMINAL THREAD SIZE | 0.500 INCHES |
THSD | THREAD SERIES DESIGNATOR | UN |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
AEFP | NONTURN DEVICE RADIUS | 0.641 INCHES MINIMUM AND 0.671 INCHES MAXIMUM |
ADAT | BODY WIDTH | 2.265 INCHES MAXIMUM |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
AEFQ | NONTURN DEVICE LENGTH | 0.115 INCHES MINIMUM AND 0.145 INCHES MAXIMUM |
ADAQ | BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.515 INCHES MINIMUM AND 1.545 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.232 INCHES MAXIMUM |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2100.0 AC ALL LOCATIONS |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
CMLP | THREAD QUANTITY PER INCH | 32 |
ABXD | BUSHING LENGTH | 0.480 INCHES MINIMUM AND 0.510 INCHES MAXIMUM |
AEFS | NONTURN DEVICE DIAMETER | 0.151 INCHES MINIMUM AND 0.161 INCHES MAXIMUM |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |