Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
12436 | BAE SYSTEMS NATIONAL SECURITY SOLUTI |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES NOMINAL |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.574 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.266 INCHES NOMINAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
ABHP | OVERALL LENGTH | 2.000 INCHES NOMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 2 TAB W/SCREW |
ADAT | BODY WIDTH | 1.250 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 7.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 70.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 30.0 DC SINGLE LOCATION |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 600.0 DC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 77.0 DEG FAHRENHEIT NOMINAL SINGLE LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES DC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |