National Stock Number (NSN) Output Data
NSN:
NIIN:
Item Name:
PANEL , POWER DISTRIBUTION
Definition:
A PANEL DESIGNED FOR CONNECTING, DISCONNECTING AND PROTECTING POWER LINE FEEDERS AND/OR DIRECT CONTROL OF SPECIFIC ELECTRIC DEVICES SUCH AS LIGHTS, MOTORS, ELECTRONIC EQUIPMENT, ETC. SEE ALSO FUSE BOX; SWITCH BOX; DISTRIBUTION BOX; AND PANEL, POWER BUS, CIRCUIT BREAKER.
Reference/Part Number
Part Number | CAGE | Status | RNCC | RNVC | DAC | RNAAC | MSDS | SADC |
---|---|---|---|---|---|---|---|---|
6002607 | 80091 | A | 3 | 2 | 1 | JN |
CAGE Information
Code | Company |
---|---|
80091 | NAVAL FACILITIES ENGINEERING COMMAND |
Federal Supply Class
Title
ELECTRICAL CONTROL EQUIPMENT
Inclusions:
INCLUDES CONTACTORS; MOTOR CONTROLLERS; POWER SERVOMECHANISMS; SWITCHGEAR; VOLTAGE REGULATORS.
Exclusions:
EXCLUDES AUTOMATIC PILOT MECHANISMS; RELAYS; RESISTORS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
APPY | INPUT FREQUENCY IN HERTZ | 60.0 |
APPY | INPUT FREQUENCY IN HERTZ | 60.0 |
APNW | ELECTRICAL INPUT QUANTITY | 1 |
ABHP | OVERALL LENGTH | 72.000 INCHES MAXIMUM |
APNX | INPUT VOLTAGE RATING | 480.0 AC POUNDS PER HOUR WITH RETAINING CHAIN |
ZZZT | NONDEFINITIVE SPEC/STD DATA | II TYPE AND 1 CLASS |
FAAZ | PHASE | THREE |
ANJG | PANEL MATERIAL | ALUMINUM |
ABMK | OVERALL WIDTH | 36.000 INCHES MAXIMUM |
ANPM | INPUT PHASE | THREE |
ANPZ | INCLOSURE FEATURE | WATERPROOF |
APPA | OUTPUT VOLTAGE RATING | 120.0 AC VOLTS MINIMUM AND 208.0 AC VOLTS MAXIMUM |
APNZ | ELECTRICAL OUTPUT QUANTITY | 7 |
APCA | PANEL QUANTITY | 1 |
ANSQ | OUTPUT FREQUENCY RATING | 60 HERTZ |
ADJH | MOUNTING METHOD | FLOOR |
FEAT | SPECIAL FEATURES | PORTABLE ASSEMBLED UNIT,650 LB MAX WT,LIFTABLE BY FORK LIFT,CONSISTS OF 5 480V CIRCUITS OF 2 3-POLE 225 AMP CIRCUIT BREAKERS W/LUGS ONLY,1 3-POLE 30 AMP CIRCUIT BREAKER FEEDING THE INPUT SIDE OF A 15KVA 480 DELTA,208/120V,3 PHASE,DRY TRANSFORMER,1 2-POLE 100 AMP AND 2 2-POLE 50 AMP CIRCUIT BREAKERS W/LUGS ONLY TO BE CONNECTED ON THE 208/120V SIDE OF THE TRANSFORMER,2 3-POLE 30 AMP CIRCUIT BREAKERS PROTECTING TWO RECEPTACLES,NEMA CONFIGURATION L21-30R AND 14 1-POLE 20 AMP CIRCUIT BREAKERS OF THE GROUND FAULT TYPE,UL APPROVED,PROTECTING FOURTEEN RECEPTACLES,NEMA CONFIGURATIONS L5-20R,GROUND LUG TO ACCOMMODATE A NO. 1 OR 2 AWG COPPER WIRE,ALL CIRCUIT BREAKERS TO CONFORM TO FED SPEC W-C-375 |
ABKW | OVERALL HEIGHT | 40.000 INCHES MAXIMUM |