Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
74193 EATON CORP HEINEMANN PRODUCTS COMMER

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ADAT BODY WIDTH 4.500 INCHES NOMINAL
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 3.000 NOMINAL AT 300 PCT ALL LOCATIONS AND 1.500 NOMINAL AT 400 PCT ALL LOCATIONS
ADAQ BODY LENGTH 5.250 INCHES NOMINAL
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 4.359 INCHES NOMINAL
AKPX POLE QUANTITY 3
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED EXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1500.0 AC ALL LOCATIONS
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 40.000 NOMINAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.984 INCHES NOMINAL
ADAU BODY HEIGHT 2.687 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
AJEC BOSS HEIGHT 0.219 INCHES NOMINAL
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.190 INCHES NOMINAL
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.000 INCHES NOMINAL
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.359 INCHES NOMINAL
THSD THREAD SERIES DESIGNATOR UNC
AXHR MOUNTING FACILITY TYPE AND QUANTITY 12 THREADED HOLE AND 12 UNTHREADED HOLE
CPRJ TRIP RELEASE METHOD MAGNETIC ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
CQJX NOMINAL THREAD SIZE 0.164 INCHES
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 THREADED STUD
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 32
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 416.0 AC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 50.0 AMPERES AC ALL LOCATIONS

Similar Parts

64-964EMG4-50AMP , 64964EMG450AMP , 5925-00-755-5080 , 5925007555080 , 007555080