Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
74193 EATON CORP HEINEMANN PRODUCTS COMMER

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 230.0 AC SINGLE LOCATION
ADAQ BODY LENGTH 2.540 INCHES MAXIMUM
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 4.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 12.000 MAXIMUM AT 200 PCT SINGLE LOCATION
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC SINGLE LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
CPRZ AUXILIARY SWITCH FUNCTION AND QUANTITY 1 ALARM
AAQL BODY STYLE SINGLE POLE TYPE
TTQY TERMINAL TYPE AND QUANTITY 2 THREADED STUD
ADAT BODY WIDTH 0.750 INCHES NOMINAL
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.060 INCHES NOMINAL
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED MOISTURE RESISTANT AND FUNGUS RESISTANT
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.970 INCHES MAXIMUM
CSSX SWITCH CURRENT RATING AND TYPE IN AMPS 2.5 AC
AEGJ SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
CQSM SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE ONE
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.770 INCHES MAXIMUM
ADTV CASE MATERIAL PLASTIC
AKPX POLE QUANTITY 1
AJEC BOSS HEIGHT 0.140 INCHES NOMINAL
CPRQ RESET METHOD MANUAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED HOLE
THSD THREAD SERIES DESIGNATOR UNC
CRTK SWITCH TERMINAL TYPE TAB, SOLDER LUG
CPRW ACTUATOR FUNCTION TRIP-RESET
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 12.5 AMPERES AC SINGLE LOCATION
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE
CSWP SWITCH VOLTAGE RATING AND TYPE IN VOLTS 250.0 AC
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CMLP THREAD QUANTITY PER INCH 32
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 SINGLE LOCATION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC SINGLE LOCATION
CQJX NOMINAL THREAD SIZE 0.138 INCHES

Similar Parts